PofoliaShared via Pofolia

Processes· 2026Q2

Stability Analysis and Enhancement of Grid-Following Offshore Wind Farms Integrated via Flexible Low-Frequency AC Transmission Considering Multi-Control-Loop Bandwidth Interaction

Yi Lu, Ziming Li, Jiachuan You, Yanxia Yao et al.

Short summary

A novel coordination strategy, implemented via controller parameter tuning, enhances the stability of grid-following offshore wind farms connected via flexible low-frequency AC transmission (LFTS) by separating control loop bandwidths.

AI-generated from the title and abstract; the full text is not read.

Key points

  • A unified small-signal model integrates grid-following wind farms, LFTS, M3C converters, and the receiving grid.
  • A dominant 30 Hz mode, linked to phase-locked loop, wind-farm outer loops, M3C voltage control, and transmission network dynamics, was identified.
  • A coordination strategy based on bandwidth separation enhances stability by tuning controller parameters.
  • Simulations confirm the strategy suppresses oscillations and improves stability, showing a higher power-transfer boundary than PLL retuning at SCR = 1.50.

AI-generated from the title and abstract; the full text is not read.

Abstract

A flexible low-frequency AC transmission system (LFTS) can extend the AC export range of offshore wind farms, but interactions among converter control loops may restrict its stable operating region. This paper develops a unified small-signal model comprising a grid-following wind farm, low-frequency cable, modular multilevel matrix converter (M3C), and receiving grid. A matrix-valued generalized Nyquist return ratio, together with modal participation and parameter-sensitivity analyses, indicates that the approximately 30 Hz dominant mode is strongly associated with the coupled control and network dynamics involving the phase-locked loop, wind-farm outer loops, M3C low-frequency voltage control, and transmission network. Based on bandwidth separation, a coordination strategy is proposed to move the critical control dynamics away from the interaction region. Comparisons between the state-space model and MATLAB/Simulink R2023b time-domain simulations show local agreement at the tested operating points. Power-step, weak-grid, bandwidth-sweep, and parameter-variation tests show that the proposed strategy, implemented solely through controller-parameter coordination without requiring additional hardware, suppresses oscillations, improves small-signal stability, and indicates a higher representative tested power-transfer boundary than PLL retuning at SCR = 1.50; 16 and 25 MW per turbine are the respective instability test points.

The authors' abstract, as published at the source. Processes, 2026 · DOI ↗

TakeawaysPremium
Ask the paperFree account

Continue with a free account

Ask the paper: 3 free questions a day about this paper; save it, get its citation, new summaries every day for your field. Takeaways are Premium.

Continue free on the web

Sign in with Google or Apple; no card needed. You come back to this paper.

On your phone:

Field: Electrical and Electronic Engineering

Electrical and Electronic EngineeringEngineering