A Damage-Spectrum Framework for Specifying the Indoor Climate of Historic Buildings

Rui Li, Wanxiang Yao, Weijun Gao, Chao Liu

Short summary

A new framework decomposes indoor climate specifications for historic buildings into temperature policy, humidity guard rails, and fluctuation corridors, revealing that abandoning fixed temperature set points can reduce control energy by 86% on average while maintaining conservation risk.

AI-generated from the title and abstract; the full text is not read.

Key points

  • A novel framework decomposes indoor climate specifications into temperature policy, humidity guard rails, and fluctuation corridors.
  • Abandoning fixed temperature set points, rather than humidity controls, yields significant energy savings (average 86%) for historic buildings.
  • Conservation risk is modeled by placing mechanical fatigue, mould germination, salt transition, and chemical ageing on a common frequency axis.
  • Sensor position within a single building can cause up to a six-fold difference in specified climate tolerances.
  • The study proposes a 'rails-first' protocol and object-matched rules for EN 15757.

AI-generated from the title and abstract; the full text is not read.

Abstract

Indoor climate specifications for historic buildings prescribe temperature and relative humidity together, obscuring the conservation and energy effects of each component. This study decomposed a specification into a temperature policy, humidity guard rails and a fluctuation corridor, and tested which part governs modelled conservation risk and energy use. The analysis placed mechanical fatigue, mould germination, salt transition and chemical ageing on a common frequency axis. A reduced-order hygrothermal model, checked against measured indoor records, was optimised at equal modelled risk for 300 climate–building cases, and multi-sensor records from a historic museum and a cathedral vault quantified the effect of sensor position. The four mechanisms responded to separable frequency bands only for thin objects. At the aggregate risk of an ASHRAE class-AA box, control energy fell by 86% on average, almost entirely because the fixed temperature set point was abandoned; guard rails contributed only a few additional percentage points of savings, and a corridor was needed only in a few hot-summer climates. When each mechanism was constrained to its class-AA box value, a corridor was needed in most climates. The specified tolerance band varied by as much as a factor of six across sensor positions within one building. A rails-first protocol and object-matched rules for EN 15757 are proposed.

The authors' abstract, as published at the source. Buildings, 2026 · DOI ↗

TakeawaysPremium Ask the paperFree account

Continue with a free account

Ask the paper: 5 free questions a day about this paper; save it, get its citation, new summaries every day for your field. Takeaways are Premium.

Continue free on the web

Sign in with Google or Apple; no card needed. You come back to this paper.

On your phone:

Field: Conservation

ConservationArts and Humanities