Direct-to-chip evaporative cooling: Effect of liquid delivery layer on flow maldistribution and thermal performance

Kidus Guye, Vivek V. Manepalli, Ayşenur Ateş, Samuel Lindsay Graham et al.

Short summary

Increasing liquid delivery layer (LDL) height in direct-to-chip evaporative cooling (DCEC) systems significantly reduces liquid maldistribution, with heights from 15 μm to 90 μm improving distribution by over 40x for R-1336 mzz(Z) at 2 kW and up to 32x for water at 5 kW.

AI-generated from the title and abstract; the full text is not read.

Key points

  • Increasing LDL height from 15 μm to 90 μm reduces liquid maldistribution by >40x for R-1336 mzz(Z) at 2 kW and up to 32x for water at 5 kW.
  • Hydrophobic surfaces sustain higher pressures before bursting but result in a 22 °C higher substrate temperature than hydrophilic surfaces at equal heat loads.
  • A combined performance metric is introduced to optimize both thermal resistance and liquid maldistribution in LDL design.
  • Findings highlight the strong coupling between hydraulic resistance, liquid distribution, and thermal performance in DCEC systems.

AI-generated from the title and abstract; the full text is not read.

Abstract

The increasing power density of modern electronic devices has driven the need for advanced cooling technologies capable of dissipating high heat fluxes. Direct-to-chip evaporative cooling (DCEC) employs arrays of hollow micropillars to enable efficient phase-change heat transfer, integrated with a liquid delivery layer (LDL). The LDL plays a critical role in governing the hydraulic and thermal performance of the DCEC system. In this study, a combined experimental and numerical investigation is conducted to examine the effects of LDL geometry and evaporator surface wettability on DCEC performance. Visualization experiments are used to analyze droplet formation and flow behavior, while numerical simulations quantify pressure drop and liquid distribution across different LDL configurations. The wettability study shows that hydrophobic surfaces can sustain higher pressures before bursting. However, thermal measurements indicate a 22 °C higher substrate temperature compared to hydrophilic surfaces at the same heat load. Numerical results further demonstrate that increasing the LDL height from 15 μ m to 90 μ m reduces liquid maldistribution by more than 40 × for R-1336 mzz(Z) at 2 kW and up to 32 × for water at 5 kW. The relationship between thermal resistance and liquid maldistribution is evaluated using a combined performance metric introduced for the LDL, enabling simultaneous optimization of thermal and hydraulic performance. These findings highlight the strong coupling between hydraulic resistance, liquid distribution, and thermal performance, and provide design guidelines for hollow micropillar-based DCEC systems operating under high heat flux conditions.

The authors' abstract, as published at the source. Applied Thermal Engineering, 2026 · DOI ↗

TakeawaysPremium Ask the paperFree account

Continue with a free account

Ask the paper: 5 free questions a day about this paper; save it, get its citation, new summaries every day for your field. Takeaways are Premium.

Continue free on the web

Sign in with Google or Apple; no card needed. You come back to this paper.

On your phone:

Field: Mechanical Engineering

Mechanical EngineeringEngineering