IEEE Transactions on Power Electronics· 2015Q1· Review
DC Microgrids–Part I: A Review of Control Strategies and Stabilization Techniques
- 1,536citations
- Q1SCImago
- 2015year
Short summary
DC microgrids can be destabilized by tightly regulated point-of-load converters introducing negative impedances that oscillate with lightly damped filters, with overall system stability defined by the source-load impedance relationship (minor loop gain).
AI-generated from the title and abstract; the full text is not read.
Key points
- DC microgrid control is categorized into local (local measurements only) and coordinated (requiring communication) strategies.
- Coordinated control further divides into decentralized (local measurements), centralized, and distributed (relying on digital communication).
- Tightly regulated point-of-load converters can decrease stability margins by introducing negative impedances.
- System stability is determined by the source and load impedance relationship, known as the minor loop gain.
AI-generated from the title and abstract; the full text is not read.
Abstract
This paper presents a review of control strategies, stability analysis, and stabilization techniques for dc microgrids (MGs). Overall control is systematically classified into local and coordinated control levels according to respective functionalities in each level. As opposed to local control, which relies only on local measurements, some line of communication between units needs to be made available in order to achieve the coordinated control. Depending on the communication method, three basic coordinated control strategies can be distinguished, i.e., decentralized, centralized, and distributed control. Decentralized control can be regarded as an extension of the local control since it is also based exclusively on local measurements. In contrast, centralized and distributed control strategies rely on digital communication technologies. A number of approaches using these three coordinated control strategies to achieve various control objectives are reviewed in this paper. Moreover, properties of dc MG dynamics and stability are discussed. This paper illustrates that tightly regulated point-of-load converters tend to reduce the stability margins of the system since they introduce negative impedances, which can potentially oscillate with lightly damped power supply input filters. It is also demonstrated that how the stability of the whole system is defined by the relationship of the source and load impedances, referred to as the minor loop gain. Several prominent specifications for the minor loop gain are reviewed. Finally, a number of active stabilization techniques are presented.
The authors' abstract, as published at the source. IEEE Transactions on Power Electronics, 2015 · DOI ↗
Continue with a free account
Ask the paper: 3 free questions a day about this paper; save it, get its citation, new summaries every day for your field. Takeaways are Premium.
Continue free on the webSign in with Google or Apple; no card needed. You come back to this paper.
On your phone:
Field: Control and Systems Engineering
Control and Systems EngineeringEngineering