Techno-Economic Sizing and Hierarchical Control of a Hybrid Energy Storage System for Renewable Energy Integration: A Case Study of the Apulia Region

Mohamed Khaled Kasseb, Shehzad Ahmad, Marco Faifer

Short summary

A hybrid energy storage system (HESS) combining Lithium-ion batteries (150 MW/600 MWh) and supercapacitors (492 MW/1.75 MWh) improved grid stability in Apulia, Italy, by raising frequency nadir 0.21–0.57 Hz and lowering RoCoF by 41% in simulations.

AI-generated from the title and abstract; the full text is not read.

Key points

  • A 150 MW/600 MWh battery and 492 MW/1.75 MWh supercapacitor HESS was sized for the Apulia region.
  • A "Supercapacitor-First" hierarchical control strategy prioritizes grid stability.
  • Simulations show HESS raised frequency nadir by 0.21–0.57 Hz in four contingencies.
  • HESS lowered maximum rate of change of frequency from 1.56 to 0.91 Hz/s.
  • Battery throughput and micro-cycles were reduced by 9% and 19%, respectively.

AI-generated from the title and abstract; the full text is not read.

Abstract

The global transition to sustainable energy has accelerated the deployment of renewable energy sources, particularly solar photovoltaic and wind power. However, the inherent variability of these resources introduces significant stability challenges to power systems, including frequency deviations and supply-demand imbalances. This study proposes and analyzes a Hybrid Energy Storage System (HESS) that synergistically combines the high energy density of Lithium-ion batteries with the high-power density of supercapacitors. The proposed architecture is designed to address the specific grid constraints of the Apulia region in Southern Italy, a renewable energy hub where generation frequently exceeds local demand. A techno-economic sizing methodology and simulation framework are employed to dimension a 150 MW/600 MWh battery energy storage system complemented by a 492 MW/1.75 MWh supercapacitor bank for millisecond-level transient power management. A three-layer hierarchical control strategy is developed to resolve conflicting operational objectives, implementing a “Supercapacitor-First” dispatch protocol that prioritizes grid stability, followed by system restoration and economic energy arbitrage. This proposed architecture is validated through deterministic time-domain simulation; results demonstrate that the HESS raises the frequency nadir by 0.21–0.57 Hz in four contingencies, lowers the maximum rate of change of frequency from 1.56 to 0.91 Hz/s, and reduces battery throughput by 9% and micro-cycles by 19% at baseline load. The SC investment is not recovered under current Italian market rules, but it is recovered in 11 years with a European fast-frequency mechanism. Its viability therefore depends on the market remunerating fast frequency response.

The authors' abstract, as published at the source. Energies, 2026 · DOI ↗

TakeawaysPremium
Ask the paperFree account

Continue with a free account

Ask the paper: 3 free questions a day about this paper; save it, get its citation, new summaries every day for your field. Takeaways are Premium.

Continue free on the web

Sign in with Google or Apple; no card needed. You come back to this paper.

On your phone:

Field: Energy Engineering and Power Technology

Energy Engineering and Power TechnologyEnergy